Chapter 2 Specification of Communication port for CPU module
2 – 49
(C) Sequence
An example of a communication sequence using the Omron-made modem ME3314A is shown below.
[1] Receiving sequence
Modem
EHV-CPU
Mode,
EHV-CPU
Modem
EHV-CPU
AT E 0 Q0 V 0 & C 1 & S0 CR LF
0 CR
Waiting for receiving
2 CR
Forced connection when 3 rings detected
2 CR2 CR
1 CR
Receiving complete
Port communication begins from here
ATA CR
LF
DR on
ER on
Initial setting (*1)
(a)
(b)
(c)
(d)
(a) The PLC generates the AT command for performing the initial setting.
(b) If the initial setting is OK, the modem returns “0”.
(c) The PLC detects the result code “2” three times in the status waiting for receiving.
(d) Connects the modem.
[2] Disconnect sequence
M
ode
m
EHV-CPU
3 CR
Line disconnected (*2)
Port communication end
(a)
(a) The PLC disconnects the line if the result code “3” is returned form the modem.
*1: The initial setting for modem by EHV-CPU sets the minimal items as follows. Therefore, please
set the modem by the AT command connecting a personal computer with the modem before
connecting with EHV-CPU. (Set the DR signal to always ON.) However, do not change the
following initial setting.
Initial setting contents
Command echo : Excluding
Result code : Including
Result code display forma : Number format
*2: Please generate a task code (H1C) of the disconnected request from the host side before
disconnecting the line in practice.