Chapter 2 Specification of Communication port for CPU module
2 – 15
(2) Event transmitting completion flag [2] and Event transmitting request flag [B]
If user turns on the event transmitting request flag [B] when message data can be transmitted and received (the
connection is established in TCP/IP, and ASR port is opened in UDP/IP), the system will transmit message data. If the
transmitting of message data is completed, the system will turn on the event transmitting completion flag [2]. If user
performs the event transmitting again, user must turn on the event transmitting request flag [B] after turning OFF. And
when monitoring whether the transmitting to the event transmitting request has been completed or not, user needs t
turn off the event transmitting completion flag before turning on the event transmitting request flag.
If the event transmitting request flag [B] is turned ON when message data cannot be transmitted and received (the
connection is not established in TCP/IP, and ASR port is not opened in UDP/IP), the error flag and the error code are
set because of error.
[B]
[2]
Transmitting
completion
Transmitting starts if the rising o
the event transmitting is detected.
: Operation by user
: Operation by system
Turn off the flag by user if necessary.
(System does not turn off the flag.)
Figure 2.14 Event transmitting completion flag and Event transmitting request flag
(3) Receiving completion flag [3]
If the receiving of message data is completed, the receiving completion flag [3] will turn ON. Since the system turns
on this flag whenever the receiving is completed, user needs to turn off this flag when monitoring the receiving using
this flag.
[3]
Receiving completion
: Operation by user
: Operation by system
Turn off the flag by user if necessary.
(System does not turn off the flag.)
Figure 2.15 Receiving completion flag