Advant Controller 31 / Issued: 07.99
Hardware 07 KP 93 R1161
8 .3
24V
DC-IN
PE
COM3 COM4
3
15 16 17 18 19
24V DC–IN max. 2,5 W
L+ M
PE
L+ M
4
1.3.2 Connecting the 24 V DC supply voltage
The supply voltage is fed in via a 5-pole detachable termi-
nal block.
Important:
Plug and unplug terminal block only with power is
off!
1.3.3 Electrical isolation and notes on earthing
The Protective Earth is connected to the 6.3 mm Faston
terminal via a wire with a cross section of 6 mm
2
(maxi-
mum length 25 cm).
The signals of the interfaces COM3 and COM4 are elec-
trically isolated from each other and also from the internal
electronics of the unit.
The following illustration shows which parts of the unit are
connected to PE/PGND.
Supply voltage
Signal name
Terminal number
Terminal assignment:
15 L+ *) Supply voltage +24 V DC
16 L+ *) Supply voltage +24 V DC
17 M *) Reference potential (0V)
18 M *) Reference potential (0V)
19 PE Protective Earth terminal,
connected with the Faston terminal
inside the device.
Do not cause earth loops!
Connect PE and Faston to the
same earthing potential!
*) Exclusively for connection to the AC31 basic
unit (see also Figure 6)
Fig. 4: Assignment of the terminal block
for the 24 V DC-IN supply voltage
6 mm
2
cross section
Fig. 5: Electrical isolation and
notes on earthing
Connect to the
Faston con-
nector of the
basic unit
(see Fig. 6)