12
Advant Controller 31 / Issued: 07.99
Hardware 07 MK 92 R1161
8 .2
1.6 Technical data
In general, the details in section 1 System data and system structure of volume 2 of the system description Advant
Controller 31 apply as technical data. Supplementary and deviating data is listed below.
1.6.1 General data
Number of serial interfaces 4
Number of parallel interfaces 1 networking interface for connecting to the
Advant Controller 31 basic unit
Built-in application software memory Flash EPROM 128 kbytes
Diagnosis 4 configurable LEDs: LED1...4
(controlled by the application program)
Operating and error displays 3 LEDs: RUN, ERR, Supply
Conductor cross section for the max. 2.5 mm
2
removable terminals
1.6.2 Supply voltage for 07 MK 92 R1161
Rated supply voltage 24 V DC
Power dissipation typ. 2.5 W
Max. current consumption
with rated voltage 210 mA
with supply voltage 30 V 170 mA
Protection against reversed terminal connection yes (only when units with electrically isolated interfaces
are connected to COM5/COM6)
1.6.3 Connection of serial interfaces COM3, COM4
Interface standard EIA RS-232 or EIA RS-422 or EIA RS-485
Programming with 907 MK 92 via IBM-PC (or compatible)
Man-machine communication yes, e.g. with an operating station
Electrical isolation yes, interfaces with respect to each other and with
respect to the rest of the unit (also see Figure 5)
Potential differences So that no earthing potential differences arise between
the 07 MK 92 and the peripheral units connected to
COM3 and COM4, the latter are supplied from the
switch-gear cabinet mains socket (also see earthing
connections in Figure 5).
Terminal assignment and
description of the interfaces COM3, COM4 see page 7 onwards
1.6.4 Connection of serial interfaces COM5, COM6
Interface standard EIA RS-232
Man-machine communication yes, e.g. with an operating station
Electrical isolation none
Potential differences see COM3, COM4
Terminal assignment and
description of the interfaces COM5, COM6 see page 9 onwards